/ Polskie

图片展示

RCN8 Ultrasonic Heat Meter


            



  Product Features:


■  Calculator can be hung at the body or installed separately, the distance of separated installation can reach more than 10 meters,

■  Internal high capacity 3.6V lithium battery, external optional AC220V or DC24V power supply mode,

■  Special meter lever design to improve measuring accuracy & stability and reduce the requirement for straight piping during installation,

■  Protection Level is IP68,

■  Can be mounted on supply or on return pipeline and can be mounted in either horizontal or vertical direction to satisfy users’ demands,

■  Compatible with CJ/T 188, MODBUS RTU, GB/T 26831, BACnet, OMS communication protocol,

■  Support optical IrDA, RS485, M-Bus,wireless (NB-IoT, LoRa), Dual M-Bus/RS485 communication, GPRS/pulse output interfaces, convenient for user to manage data in different manners,

■  4-20 mA output mode optional,

■  Compatible to the German Heating Association Measurement NOWA protocol.


  Technical Parameter:


Nominal Diameter(mm)

50

65

80

100

Dimensions (mm)

L

200

200

225

250

D

165

185

200

220

H

245

255

280

295

K

125

145

160

180

n×D1

4×Φ18

4×Φ18

8×Φ18

8×Φ18

Weight (kg)

8

9

11

13.5

Pressure Loss(kPa/qp)

4

6

9

11

Max Flow Rate qs(m3/h)

30

50

80

120

Nominal Flow Rate qp(m3/h)

15

25

40

60

Nominal Flow Rate : Minimum Flow Rate qp/qi

100 (50 or 250 optional)

Channel

Double Channel

Flow Rate Maximum Reading(m3)

9999999.9

Heat Maximum Reading(kW·h)

99999999

Accuracy Class

Class 2

Maximum Working Pressure

1.6MPa (2.5MPa optional)

Heat Consumption Calculation

Start from 0.25K, can be customized

Protection Level

IP68

Temperature Range

(4~95)℃  ((0~150)℃ optional)

Range of Temperature Difference

(3~60)K ((2~120)K optional)

Ambient temperature

Class A (5~55) ℃ or class B (-25~55) ℃ or class C or class D optional

Power Supply

3.6V lithium battery (220V AC or 24V DC optional)

Battery Lifetime

≥10 years

Installation Method

Horizontal or Vertical Direction

Hot (Cold) Carrier

Water

Temperature Sensor

Pt1000 Platinum Resistance (Pt500 optional)


RCN8 Ultrasonic Heat Meter
适应DN50-DN100口径分体式计量使用场景

Long press to look detail
Long by picture save/share

    Tel:0631-5684698          Address:No.576, South of Torch Road, Huancui District, Weihai, Shandong Province,China